الوصف
PSTX45-600-70 Softstarter Detailed Information
Description: The softstarter PSTX45-600-70 has a rated maximum operational current of 45 A with an operating voltage span from 208 to 600 V AC. The rated control voltage is between 100 to 250 V AC at 50/60 Hz. PSTX features a three-phase control soft start and stop through a voltage or a torque ramp. It has built-in bypass for easy installation and energy saving. A RUN, TOR and Event signal is available from relay outputs in normally open state.
Functions: Current limit, kickstart, analog output, EOL, motor heating, pump cleaning, jog, braking, stand-still brake, diagnostics, sequence start, emergency/fire pump mode.
Display and Communication: Detachable full graphic display with IP66 and 4x outdoor rating. Communication via hardwire inputs Start/Stop/Reset of fault, three programmable digital inputs, built-in Fieldbus communication Modbus RTU, optional ANYBUS modules for Profinet, Profibus, Modbus TCP, Ethernet IP and others, external adaptor and Fieldbus plug.
Applications: Suitable for medium to large-sized three-phase motors with nominal currents from 30 to 1250 A inline connection or 52 to 2160 A inside delta connection. Typical applications include pumps, fans, compressors, and conveyors.
Dimensions: Width 15 cm, Height 31.4 cm, Depth 19.8 cm, Weight 4.6 kg.
Electrical Ratings: Rated operational voltage 208 to 600 V AC, control supply voltage 100 to 250 V AC, control circuit voltage 24 V DC, frequency 50/60 Hz. Operational power inline connection: 12.5 kW at 230 V, 22 kW at 400 V, 25 kW at 500 V. Operational power inside delta: 25 kW at 230 V, 37 kW at 400 V, 45 kW at 500 V.
Current Ratings: 45 A rated operational current inline, 76 A inside delta connection.
Protection and Warnings: Built-in electronic overload protection, bypass open protection, current imbalance and underload protection, dual overload for start and run, earth/ground fault protection, locked rotor protection, overs and unders voltage protection, phase reversal, power factor underload, user-defined protections, and voltage imbalance protection. Warning indications include current imbalance, electronic overload time-to-trip, faulty fan, locked rotor, over voltage, and voltage imbalance warnings.
Additional Technical Features: Auto phase sequence detection, automatic restart, limp mode, soft start/stop with torque or voltage ramp, real time clock, torque limit, and more.
Environmental: Operation ambient air temperature from -25 to +60 °C, storage temperature from -40 to +70 °C.
Degree of Protection: According to IEC 60529, IEC 60947-1, EN 60529 main terminals IP00.
Terminals: Cable clamp with main circuit hole diameter 0.85 cm, tightening torque 8 N·m.
Certifications: CQC, CCC, CE, DNV.
Customs Tariff Code: 85371091.