| الوزن |
1.75 كيلوجرام |
| الأبعاد |
21.6 × 20.7 × 15 سنتيميتر |
| Extended Product Type |
AF116-30-00-13
|
| Product ID |
1SFL427001R1300
|
| Customs Tariff Code |
85364900
|
| Number of Main Contacts NO |
3
|
| Number of Main Contacts NC |
0
|
| Number of Auxiliary Contacts NO |
0
|
| Number of Auxiliary Contacts NC |
0
|
| Number of Poles |
3P
|
| Rated Operational Voltage |
Main Circuit 690 V
|
| Rated Frequency |
Main Circuit 50 / 60 Hz
|
| Conventional Free air Thermal Current |
160 A
|
| Rated Operational Current AC 1 |
160 (40°C), 145 (60°C), 130 (70°C)
|
| Rated Operational Current AC 3 |
116 (415V, 440V, 380/400V, 220/230/240V, 55°C), 110 (500V), 65 (690V)
|
| Rated Operational Current AC 3e |
116 (415V, 440V, 380/400V, 220/230/240V, 60°C), 110 (500V), 65 (690V)
|
| Rated Operational Current DC 1 |
145 (110 V 2 Poles in Series), 145 (220 V 3 Poles in Series)
|
| Rated Operational Current DC 3 |
145 (110 V 2 Poles in Series), 145 (220 V 3 Poles in Series)
|
| Rated Operational Current DC 5 |
145 (110 V 2 Poles in Series), 145 (220 V 3 Poles in Series)
|
| Rated Operational Power AC 3 |
55 (415V), 75 (440V, 500V), 55 (690V, 380/400V), 30 (220/230/240V)
|
| Rated Operational Power AC 3e |
55 (415V), 75 (440V, 500V), 55 (690V, 380/400V), 30 (220/230/240V)
|
| Rated Breaking Capacity AC 3 |
8 x Ie AC-3
|
| Rated Breaking Capacity AC 3e |
8.5 x Ie AC-3e
|
| Rated Making Capacity AC 3 |
10 x Ie AC-3
|
| Rated Making Capacity AC 3e |
12 x Ie AC-3e
|
| Short Circuit Protective Devices |
gG Type Fuses 250 A
|
| Rated Short time Withstand Current Low Voltage |
160 A (10s), 379 A (30s), 928 A (1s), 1160 A (1min), 536 A (15 min) at 40°C ambient in free air from cold state
|
| Maximum Breaking Capacity |
2000 A at 440 V (cos phi=0.45 with cos phi=0.35 for Ie > 100 A), 1000 A at 690 V
|
| Rated Insulation Voltage |
1000 V (IEC 60947-4-1 and VDE 0110 Gr. C), 600 V UL/CSA
|
| Rated Impulse Withstand Voltage |
8 kV Main Circuit
|
| Maximum Electrical Switching Frequency |
300 cycles per hour (AC-1 and AC-3), 150 cycles per hour (AC-2 / AC-4)
|
| Mechanical Durability |
5 million
|
| Maximum Mechanical Switching Frequency |
300 cycles per hour
|
| Coil Operating Limits |
0.85 x Uc Min. to 1.1 x Uc Max. at ≤ 70 °C
|
| Rated Control Circuit Voltage |
100 – 250 V (50 Hz, 60 Hz, DC)
|
| Coil Consumption |
6 V·A holding at max rated control voltage (50/60 Hz), 3 V·A or 3 W holding at DC, 130 V·A (50/60 Hz) pull-in, 135 V·A or 135 W pull-in DC
|
| Power Loss |
6 W per pole at rated operating conditions
|
| Operate Time |
37-47 ms between coil de-energization and NO contact opening; 25-55 ms between coil energization and NO contact closing
|
| Connecting Capacity Main Circuit |
Flexible 2 x 10 – 70 mm², Rigid Cu-Cable 1 x 10 – 95 mm², Rigid Cu-Cable 2 x 10 – 95 mm²
|
| Connecting Capacity Auxiliary Circuit |
Flexible with Ferrule 2x 0.75 – 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 – 2.5 mm², Solid 2 x 1 – 4 mm², Stranded 1 x 1 – 4 mm², Stranded 2 x 1 – 4 mm²
|
| Degree of Protection |
Auxiliary Terminals IP40, Coil Terminals IP20, Main Terminals IP00 per IEC 60529, IEC 60947-1, EN 60529
|
| Tightening Torque |
Cable Lug 9 N·m, Main Circuit 8 N·m
|
| Terminal Type |
Double Clamp
|
| Product Name General |
Block Contactor
|
| Maximum Operating Voltage UL CSA |
Main Circuit 600 V
|
| General Use Rating UL CSA |
160 A (600 V AC)
|
| Horsepower Rating UL CSA |
30 hp (200-208 V AC Three Phase), 20-40 hp (220-240 V AC Three Phase), 40-75 hp (440-480 V AC Three Phase), 50-100 hp (550-600 V AC Three Phase)
|
| Full Load Amps Motor Use |
96 A (440-480 V AC Three Phase), 99 A (550-600 V AC Three Phase)
|
| Ambient Air Temperature |
-25 to 50 °C close to contactor fitted with thermal overload relay; -40 to 70 °C close to contactor without thermal overload relay; -40 to 70 °C for storage
|
| Maximum Operating Altitude Permissible |
3000
|
| Conflict Minerals Reporting Template |
Available
|
| REACH Declaration |
Available
|
| RoHS Declaration |
Available, Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
|
| Toxic Substances Control Act TSCA |
Available
|
| WEEE Category |
5. Small Equipment (No External Dimension More Than 50 cm)
|
| ABB EcoSolutions |
Yes
|
| ABB Site Meeting Group Waste To Landfill Target |
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
|
| End Of Life Disassembling Instructions |
Available
|
| Environmental Product Declaration EPD |
Available
|
| Improved Energy Efficiency for Customers |
Product requires less energy to operate compared to similar product on market or older products from the same line
|
| Recyclability Rate of the Product acc to EN45555 |
87.8 %
|
| Sustainable Material Content in Product wt percentage |
Recycled Metal – 37 %
|
| Package Level 1 Units |
box 1 piece
|
| Package Level 1 Width |
20.7
|
| Package Level 1 Depth Length |
21.6
|
| Package Level 1 Height |
15
|
| Package Level 1 Gross Weight |
1.75
|
| Package Level 1 EAN |
7320500476406
|
| Object Classification Code |
Q
|
| ETIM 7 |
EC000066 – Power contactor, AC switching
|
| ETIM 8 |
EC000066 – Power contactor, AC switching
|
| ETIM 9 |
EC000066 – Power contactor, AC switching
|
| eClass |
V11.0 : 27371003
|
| UNSPSC |
39121529
|
| IDEA Granular Category Code IGCC |
4758 >> Iec Contactors
|
| E Number Finland |
3706166
|
| E Number Norway |
3210062
|
| E Number Sweden |
3210062
|
| Certificates and Declarations |
{
"A2L_Certificate_UL": "Available",
"ABS_Certificate_Sweden": "Available",
"ABS_Certificate_China": "Available",
"BV_Certificate": "Available",
"CB_Certificate_SEMKO": "Available",
"CCS_Certificate_Sweden": "Available",
"CQC_Certificate_Sweden": "Available",
"Declaration_of_Conformity_CCC": "Available",
"Declaration_of_Conformity_CE": "Available",
"Declaration_of_Conformity_UKCA": "Available",
"DNV_Certificate": "Available",
"EAC_Certificate": "Available",
"LR_Certificate": "Available",
"PRS_Certificate": "Available",
"RINA_Certificate": "Available",
"RMRS_Certificate": "Available",
"UL_Certificate": "Available",
"UL_Listing_Card": "Available"
}
|