الوصف
AF265-30-11-13 Block Contactor
The AF265-30-11-13 is a 3 pole 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 132 kW / 400 V AC (AC-3) or 200 hp / 480 V UL and switching power circuits up to 400 A (AC-1) or 350 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be extended with add-on auxiliary contact blocks and a wide range of accessories. Includes Mounting kit with screws, washers, and sockets.
Dimensions: Width 14 cm, Depth 18 cm, Height 22.5 cm, Weight 3.9 kg.
Electrical Ratings & Performance:
Number of Poles: 3P; Main Contacts NO: 3; Main Contacts NC: 0; Auxiliary Contacts NO: 1; Auxiliary Contacts NC: 1.
Rated Operational Voltage (Main Circuit): 1000 V; Frequency: 50 / 60 Hz; Conventional Free-air Thermal Current (Ith): 400 A.
Rated Operational Currents AC-1: up to 350 A at 1000 V (40 °C), down to 240 A at 1000 V (70 °C), and various ratings at 690 V.
Rated Operational Currents AC-3: up to 265 A at 415-440 V, down to 113 A at 1000 V.
Rated Operational Currents DC-1/DC-3/DC-5: 350 A at 110/220 V with poles in series at 40 °C.
Rated Operational Power AC-3: from 75 kW at 220 V up to 200 kW at 690 V.
Rated Breaking Capacity AC-3: 8 times Ie; Making Capacity AC-3: 10 times Ie.
Short-Circuit Protective Devices: gG Type Fuses 500 A.
Rated Short-time Withstand Current Low Voltage (Icw): ranges from 400 A to 2650 A depending on duration and conditions.
Maximum Breaking Capacity: 3800 A at 440 V, 3300 A at 690 V with cos phi 0.45 or 0.35 for Ie > 100 A.
Insulation Voltage: 1000 V; Impulse Withstand Voltage: 8 kV.
Switching Frequencies: Mechanical and electrical limits specified, max 300 cycles per hour for AC-1 and AC-3.
Mechanical Durability: 5 million operations.
Coil Operating Voltage (Uc): 100-250 V AC/DC; Coil Power Consumption: Holding ~17.5 V·A (AC), 4.5 W (DC); Pull-in ~385 V·A (AC), 410 W (DC).
Power Loss per Pole: 14 W.
Operate Times: Opening 37-47 ms; Closing 25-55 ms.
Connection Capacity: Flexible and rigid cables with specified mm² ranges for main and auxiliary circuits.
Degree of Protection: Coil Terminals IP20, Main Terminals IP00 (IEC standards).
Tightening Torque: Cable Lug 28 N·m; Main Circuit 22-43 N·m.
Terminal Type: Main Circuit Bars.
UL/CSA Ratings: NEMA Size 5, Continuous Current 270 A, Full Load Amps 240 A at 440-480 V, 242 A at 550-600 V.
Horsepower Ratings UL/CSA: 75 hp to 250 hp across 200 V to 600 V AC three-phase.
Max Operating Voltage UL/CSA: 1000 V; General Use Rating: 350 A at 1000 V AC.
Environmental Data: Ambient temperatures from -25 to 70 °C depending on configuration, max operating altitude 3000 m.
Compliance & Certifications: Conflict Minerals, REACH, RoHS compliant; WEEE Category 5; Environmental Product Declaration available. Product considered energy efficient with 76.3% recyclability rate and 33% recycled metal content.
Customs Tariff Code: 85364900.