الوصف
SH204-C6 Miniature Circuit Breaker
Manufacturer: ABB
Type: SH200 – 4P – 6 A – C – (AC) 6 kA
Compact Home SH200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B, C), configurations (1P, 1P+N, 2P, 3P, 3P+N, 4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 40 A). All MCBs of the product range SH200 comply with IEC/EN 60898-1, allowing the use for residential applications.
Technical Specifications
Dielectric Test Voltage: 2 kV (50 / 60 Hz – 1 min)
Power Supply Connection: Arbitrary
Contact Position Indication: ON / OFF
Energy Limiting Class: 3
Electrical Endurance: 20000 AC cycle
Mechanical Endurance: 20000 cycle
Number of Protected Poles: 4
Number of Poles: 4
Tightening Torque: 2 N·m
Actuator Type: Toggle
Screw Terminal Type: Cage Terminal
Actuator Marking: I / O
Actuator Material: Insulation Group II, Black, Sealable
Recommended Screw Driver: Pozidriv 2
Connecting Capacity Flexible with Ferrule: 0.75 – 16 mm²
Connecting Capacity Rigid: 0.75 – 25 mm²
Installation Size: acc. to DIN 43880 1
Terminal Type: Screw Terminals
Electrical Ratings
Tripping Characteristic: C
Rated Operational Voltage: 400 V AC according to IEC 60898-1
Operational Voltage: 12 – 440 V AC
Rated Insulation Voltage (Ui): 440 V
Rated Impulse Withstand Voltage (Uimp): 4 kV (5 kV at 2000 m altitude, 6.2 kV at sea level)
Input Voltage Type: AC
Rated Current (In): 6 A
Rated Short-Circuit Capacity: 6 kA (AC, 400 V)
Rated Conditional Short-Circuit Current (Inc): 6 kA (230 V / 400 V)
Rated Frequency: 50 / 60 Hz
Power Loss: 8 W total, 2 W per pole
Overvoltage Category: III
Design and Compliance
Housing Material: Insulation Group II, RAL 7035
RoHS Compliance: Following EU Directive 2011/65/EU and Amendment 2015/863
REACH Compliance: Does not contain substances above 0.1 mass percentage
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm), Business To Business
Environmental Conditions
Ambient Air Temperature: Operation: -25 to +55 °C, Storage: -40 to +70 °C
Reference Ambient Air Temperature: 30 °C
Degree of Protection: IP20 (IP40 enclosure with cover)
Pollution Degree: 2
Environmental Conditions: 28 cycles with 55 °C / 90-96 % relative humidity and 25 °C / 95-100 % relative humidity
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz
Resistance to Shock (IEC 60068-2-27): 25g, 2 shocks, 13 ms
Dimensions and Weight
Width: 7 cm
Height: 8.5 cm
Depth / Length: 6.9 cm
Built-In Depth: 6.9 cm
Net Weight: 0.408 kg
Pole Net Weight: 0.115 kg
Mounting
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) and TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position: any
Installation Size: acc. to DIN 43880 1
Standards and Certifications
Standards: IEC/EN 60898-1
Certification Agency: EN, IEC
ETIM 9 / 10 Class: EC000042 – Miniature circuit breaker (MCB)
UNSPSC Code: 39121603
eClass: V11.0 : 27141901
IDEA Granular Category Code (IGCC): 4897 >> Miniature circuit breakers
Object Classification Code: F