الوصف
Product: Circuit breaker, ComPacT NSX400N, 50kA/415VAC, 3 poles, MicroLogic 2.3 trip unit 400A
This ComPacT NSX400N is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 50 kA rms at 415 VAC 50/60Hz. The operational voltage is 690 VAC 50/60 Hz. This product embeds an electronic MicroLogic 2.3 trip unit, with 400 A rating. MicroLogic 2.3 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 3 poles version (14 cm x 25.5 cm x 11 cm) comes with a variety of optional functions and accessories. It is compliant with international standards IEC 60947, CCC, EAC and marine specifications. ComPacT NSX400N is part of Schneider Electric EcoStruxure Power architecture.
Specifications
Range: ComPacT NSX, new generation
Device short name: NSX400N
Type: Circuit breaker
Device application: Distribution
Poles description: 3P
Protected poles description: 3D
Rated current In: 400 A at 40 °C
Rated operational voltage Ue: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1; 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1; 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity code: N 50 kA 415 V AC
Trip unit name: MicroLogic 2.3
Trip unit technology: Electronic
Trip unit protection functions: LSoI
Control type: Toggle
Circuit breaker mounting mode: Fixed
Main
Rated insulation voltage Ui: 800 V AC 50/60 Hz
Rated impulse withstand voltage Uimp: 8 kV
Rated service breaking capacity Ics: 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 15000 cycles
Electrical durability: 12000 cycles at 440 V In/2; 6000 cycles at 440 V In; 6000 cycles at 690 V In/2; 3000 cycles at 690 V In
Power dissipation per pole: 19.2 W
Mounting support: Backplate
Mounting position: Horizontal and vertical; Flat on the back
Upside connection: Front
Downside connection: Front
Connection pitch: 4.5 cm
Protection type: L : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating: 400 A at 40 °C
Long-time pick-up adjustment type Ir: Adjustable 9 settings
Long-time protection pick-up adjustment range: 160 to 400 A
Long-time protection delay adjustment type tr: Fixed
Long-time delay adjustment range: 400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd: Adjustable 9 settings
Short-time protection pick-up adjustment range: 1.5 to 10 x Ir
Short-time protection delay adjustment type tsd: Fixed
Instantaneous protection pick-up adjustment type Ii: Fixed
Instantaneous protection pick-up adjustment range: 4800 A
Earth-leakage protection: Without
Zone selective interlocking ZSI: Without
Number of slots: 6
Local signalling: Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Width (W): 14 cm
Height (H): 25.5 cm
Depth (D): 11 cm
Net weight: 6.05 kg
Complementary
Standards: EN/IEC 60947-2
Overvoltage category: III
Electrical shock protection class: Class II on front face
Pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
Ambient air temperature for operation: -25 to 70 °C
Ambient air temperature for storage: -50 to 85 °C
Relative humidity: 0 to 95 %
Operating altitude: 0 to 2000 m without derating; 2000 to 5000 m with derating
Packaging
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 15 cm
Package 1 Width: 16 cm
Package 1 Length: 29.2 cm
Package 1 Weight: 5.369 kg
Unit Type of Package 2: S04
Number of Units in Package 2: 2
Package 2 Height: 30 cm
Package 2 Width: 40 cm
Package 2 Length: 60 cm
Package 2 Weight: 11.438 kg
Warranty
18 months.
Customs Tariff Code: 85362000