الوصف
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Description
Eaton Moeller series Power Defense – Molded Case Circuit Breaker. Circuit breaker, 40 A, 25 kA, 1p, box terminal
Dimensions & Weight
Length/Depth: 8.8 cm; Height: 14.5 cm; Width: 3 cm; Weight: 0.386 kg
Electrical Specifications
Voltage rating: 230 V – 230 V; Max. rated operation voltage Ue AC: 230 V; Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V; Rated impulse withstand voltage (Uimp) at main contacts: 6000 V;
Rated current (Iu): 40 A; Instantaneous current setting (Ii) min: 40 A; Instantaneous current setting (Ii) max: 350 A; Overload current setting (Ir) min: 32 A; Overload current setting (Ir) max: 40 A;
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 18 kA; Short-circuit total breaktime: < 10 ms;
Electrical connection type of main circuit: Frame clamp; Isolation: 500 V AC (between auxiliary contacts and main contacts) 300 V AC (between the auxiliary contacts); Overvoltage category: III; Utilization category: A; Pollution degree: 3
Mechanical Specifications
Type: Circuit breaker; Release system: Thermomagnetic release;
Mounting Method: Fixed DIN rail (top hat rail) mounting optional Complete device in housing;
Degree of protection: IP2X IP20 (basic degree of protection, in the operating controls area); Front side: IP40 (with insulating surround) IP66 (with door coupling rotary handle); Terminations: IP10 (tunnel terminal) IP00 (terminations, phase isolator and band terminal);
Shock resistance: 20 g (half-sinusoidal shock 20 ms); Number of auxiliary contacts (change-over, normally closed, normally open): 0; Number of operations per hour – max: 120;
Handle type: Rocker lever; Position of connection for main current circuit: Front side; Direction of incoming supply: Vertical and 90° in all directions; Standard terminals: Box terminal;
Climatic proofing: Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30; Lifespan, mechanical: 20000 operations
Operating Conditions
Ambient operating temperature: -25 °C min, 70 °C max; Ambient storage temperature: -40 °C min, 70 °C max
Standards & Compliance
Certifications: IEC IEC/EN 60947; Compliances: RoHS conform; Customs Tariff Code: 85362010
Additional Information
Features: Protection unit; Functions: System and cable protection; Special features: Fixed overload releases Ir