الوصف
FH202 AC-40/0.03
Manufacturer: ABB
Product ID: 2CSF202006R1400
EAN: 8012542894308
Type of Residual Current: Type AC
Rated Service Short-Circuit Breaking Capacity (Ics): 1 kA
Maximum Surge Current: 0.25 kA
Leakage Current Type: AC
Electrical Endurance: 10000 cycles
Mechanical Endurance: 20000 cycles
Number of Poles: 2
Number of Modular Spacings per DIN Rail: 2
Operating Characteristic: Instantaneous
Options Provided: None
Accessories Available: No
Rated Cross-Section Multi-Wired: 10…25 mm²
Rated Cross-Section Solid-Core: 25…25 mm²
Rated Voltage (Ur): 230 V
Rated Operational Voltage: 230 V
Rated Insulation Voltage (Ui): 500 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
Rated Current (In): 40 A
Rated Residual Current: 30 mA
Rated Conditional Short-Circuit Current (Inc): 6 kA
Rated Frequency (f): 50 Hz
Power Loss: Total 4.8 W, at Rated Operating Conditions per Pole 2.4 W
Number of Modules: 2
RoHS Date: 20211115
REACH Date: 20240429
Conflict Minerals Reporting Template: 719d39e9-c62c-4c41-a6dc-53de2a11e8ea Italy
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B: Business To Consumer
Ambient Air Temperature Operation: -5 … +40 °C
Ambient Air Temperature Storage: -40 … +70 °C
Degree of Protection: IP2X
Dimensions (W x H x D): 3.5 cm x 8.5 cm x 6.9 cm
Built-In Depth: 6.9 cm
Product Net Weight: 0.2 kg
Package Level 1 Units: box 1 piece
Package Level 1 Gross Weight: 0.236 kg
Mounting Type: DIN-Rail
External Classifications: ETIM 9 & ETIM 10: EC000003 – Residual current circuit breaker (RCCB), eClass: V11.0 : 27142201, Object Classification Code: F
Standards: IEC 61008
Customs Tariff Code: 85362000
Catalog Description: Residual Current Circuit Breaker FH200 – 2P – 30 mA – 40 A – Type AC
Long Description: The RCCBs FH200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous AC and A types is particularly suitable for installation in domestic applications.