الوصف
Moulded Case Circuit Breaker 3P3D 63A 25kA TM adjustable h3 x160 HHA063U
Hager h3 x160 TM ADJ 3P3D MCCB, 63A, protects three-phase circuits in commercial/industrial panels. Icu 25kA at 400V (35kA at 240V), Ics 20kA at 400V (25kA at 230V) for dependable fault clearing. Adjustable thermal 0.63-1×In with TM A/F trip adapts to loads. Ue 220-415V, Ui 690V, Uimp 8kV, 50/60Hz. IP4X. Screw terminals 4-70 mm² (flex) / 4-95 mm² (rigid). Endurance: 10k electrical, 20k mechanical. Ideal for feeders and submains.
Technical Characteristics
- Rated current: 63 A
- Number of poles: 3
- Rated ultimate short-circuit breaking capacity Icu under 400V AC: 25 kA
- Rated ultimate short-circuit breaking capacity Icu under 240V AC: 35 kA
- Rated service breaking capacity Ics under 400V AC: 20 kA
- Rated service breaking capacity Ics under 230V AC: 25 kA
- Frequency: 50 – 60 Hz
- Rated impulse withstand voltage Uimp: 8000 V
- Rated insulation voltage Ui: 690 V
- Rated operational voltage Ue: 220 – 415 V
- Trip unit: TM A/F
- Power dissipation at In: 30 W
- Electrical endurance: 10000 cycles
- Mechanical operations: 20000
- IP Rating: IP4X
- Connection: Screw terminal
- Dimensions: 13 cm (Height) x 7.5 cm (Width) x 6.8 cm (Depth)