الوصف
Moulded Case Circuit Breaker h3 x160 TM FIX 1P1D 80A 18kA CTC HDA078Z
EAN-Nr.: 3250613135911
Packaging: 1 piece
Technical characteristics
Electric current
Rated current: 80 A
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-2: 18 kA
Rated service breaking capacity Ics under 230 V AC according to IEC 60947-2: 18 kA
Rated current 10°C according to IEC 60947: 106.90 A
Rated current 15°C according to IEC 60947: 103.90 A
Rated current 20°C according to IEC 60947: 100.90 A
Rated current 25°C according to IEC 60947: 97.70 A
Rated current 30°C according to IEC 60947: 94.40 A
Rated current at 35°C according to IEC 60947: 91 A
Rated current at 40°C according to IEC 60947: 87.50 A
Rated current 45°C according to IEC 60947: 83.80 A
Rated current 50°C according to IEC 60947: 80 A
Rated current 55°C according to IEC 60947: 75.90 A
Rated current at 60°C according to IEC 60947: 71.60 A
Rated current 65°C according to IEC 60947: 67.10 A
Rated current 70°C according to IEC 60947: 62.20 A
Architecture
Number of poles: 1
Control/operation element: Toggle
Device construction type: Fixed built-in
Neutral position: Without neutral
Tripping
Response time when opening: 10 ms
Frequency
Frequency: 50 – 60 Hz
Voltage
Rated impulse withstand voltage Uimp: 8,000 V
Rated insulation voltage Ui: 690 V
Functions
Trip unit: TM F/F
Power
Total power loss under IN: 4.80 W
Endurance
Electric endurance in number of cycles: 10,000
Number of mechanical operations: 20,000
Safety
Ingress Protection (IP) class: IP4X
Connection
Cross-section flexible conductor: 4 – 70 mm²
Cross-section rigid conductor: 4 – 95 mm²
Installation, mounting
Mounting-/Connection Position: Front
Connectivity
Type of connection: Screw terminal
Settings
Thermal protection knob setting xIN: 1, 1
Dimensions
Height: 130 mm
Width: 25 mm
Depth: 68 mm
Compatibility
Suitable for DIN Rail: Yes
Main electrical attributes
Magnetic protection trip time: 0 – 0 ms