الوصف
UA75-30-00RA 220-230V 50Hz / 230-240V 60Hz Block Contactor
The UA75-30-00RA 220-230V 50Hz / 230-240V 60Hz is a 3-pole contactor designed for capacitor switching, suitable for installations where the peak current far exceeds 100 times the nominal rms current. The contactors include damping resistors and must be used without additional inductances. Capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before re-energization. Electrical durability is 250000 operating cycles for Ue less than 500 V and 100000 cycles for Ue between 500 V and 690 V. The UA..RA contactors feature a front mounted block with 3 damping resistors to limit current peaks during capacitor bank energization and ensure capacitor precharging, reducing current peaks during main pole making.
Main poles: 3
Control circuit: AC operated with laminated magnet circuit
Accessories: Wide range available.
Technical Data:
Number of main contacts NO: 3
Number of main contacts NC: 0
Number of auxiliary contacts NO/NC: 0/0
Number of poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1
Rated operational voltage: Main circuit 690 V
Rated frequency: 50 / 60 Hz
Rated operational power AC-6b at 230/240 V and 40 °C: 35 kvar
Rated operational power AC-6b at 230/240 V and 55 °C: 30 kvar
Rated operational power AC-6b at 230/240 V and 70 °C: 25 kvar
Rated operational power AC-6b at 400/415 V and 40 °C: 60 kvar
Rated operational power AC-6b at 400/415 V and 55 °C: 50 kvar
Rated operational power AC-6b at 400/415 V and 70 °C: 41 kvar
Rated operational power AC-6b at 440 V and 40 °C: 65 kvar
Rated operational power AC-6b at 440 V and 55 °C: 53 kvar
Rated operational power AC-6b at 440 V and 70 °C: 45 kvar
Rated operational power AC-6b at 500/550 V and 40 °C: 75 kvar
Rated operational power AC-6b at 500/550 V and 55 °C: 65 kvar
Rated operational power AC-6b at 500/550 V and 70 °C: 55 kvar
Rated operational power AC-6b at 690 V and 40 °C: 100 kvar
Rated operational power AC-6b at 690 V and 55 °C: 80 kvar
Rated operational power AC-6b at 690 V and 70 °C: 70 kvar
Short-circuit protective devices: gG type fuses 200 A
Maximum breaking capacity at 440 V cos phi=0.45 (0.35 for Ie > 100 A): 1300 A
Maximum breaking capacity at 690 V cos phi=0.45 (0.35 for Ie > 100 A): 630 A
Rated insulation voltage (Ui): 1000 V according to IEC 60947-4-1, 600 V according to UL/CSA
Rated impulse withstand voltage (Uimp): 8 kV
Electrical durability: 250000 cycles at Ue ≤ 440 V, 100000 cycles at Ue = 500 to 690 V
Maximum electrical switching frequency: 240 cycles/hour
Rated control circuit voltage (Uc): 220-230 V at 50 Hz, 230-240 V at 60 Hz
Coil consumption average holding value: 18 V·A
Coil consumption average pull-in value: 180 V·A at 50 Hz, 210 V·A at 60 Hz
Operate time between coil de-energization and NO contact opening: 4 to 11 ms
Operate time between coil energization and NO contact closing: 8 to 27 ms
Mounting on DIN rail TH35-15 and TH75-25 acc. to IEC 60715, mounting by 2x M6 screws placed diagonally
Connecting capacity main circuit: flexible cable end 6 to 10 mm², rigid cable 6 to 16 mm²
Connecting capacity auxiliary circuit: flexible cable end 0.75 to 2.5 mm², rigid cable 1 to 4 mm²
Degree of protection: coil terminals IP20, main terminals IP10 according to IEC 60529, IEC 60947-1, EN 60529
Connecting terminals main poles: M6 (+,-) Pozidriv 2 screws with 1x (13 x 10 mm) connector
Terminal type: screw terminals
Dimensions and Weight:
Width: 7 cm
Depth/Length: 14.04 cm
Height: 15 cm
Net weight: 1.35 kg
Packaging:
Box containing 1 piece
Width: 16 cm
Depth/Length: 20 cm
Height: 8.5 cm
Gross weight: 1.35 kg
Classifications:
Object Classification Code: Q
ETIM 7/8/9: EC001079 – Capacitor contactor
eClass: V11.0 : 27371006
UNSPSC: 39121529
IDEA Granular Category Code: 4756 – Capacitor magnet contactor
E-Number (Finland): 3709168